SCB10(11) Series 10kV Dry-type transformers technical parameters | ||||||||||||
Rated Capacity kVA |
Voltage Combination | Vector group |
Off-load Loss (W) |
On-load Loss (W) (120ºC) |
Short Circuit Current (%) |
Impendance (%) |
Weight (kg) |
Dimensions(mm) | ||||
High Voltage (kV) |
Tapping Range (%) |
Low Voltage (kV) |
Total | Length | Width | Height | ||||||
30 | 6 6.3 10 10.5 11 |
±5 or ±2×2.5 |
0.38 0.4 0.415 0.433 |
Dyn11 or Yyn0 |
190/170 | 710 | 2.3 | 4 | 240 | 580 | 360 | 629 |
50 | 270/250 | 1000 | 2.2 | 315 | 650 | 360 | 664 | |||||
80 | 370/340 | 1380 | 1.7 | 420 | 780 | 460 | 684 | |||||
100 | 400/360 | 1570 | 1.7 | 485 | 840 | 460 | 729 | |||||
125 | 470/430 | 1850 | 1.5 | 590 | 870 | 460 | 754 | |||||
160 | 540/490 | 2130 | 1.5 | 690 | 880 | 460 | 764 | |||||
200 | 620/560 | 2530 | 1.3 | 820 | 960 | 920 | 786 | |||||
250 | 720/650 | 2760 | 1.3 | 965 | 1000 | 920 | 831 | |||||
315 | 880/800 | 3470 | 1.1 | 1090 | 1020 | 920 | 861 | |||||
400 | 980/890 | 3390 | 1.1 | 1285 | 108 | 970 | 906 | |||||
500 | 1160/1020 | 4880 | 1.1 | 1430 | 1100 | 1020 | 921 | |||||
630 | 1340/1180 | 5880 | 0.90 | 1705 | 1290 | 1170 | 906 | |||||
630 | 1300/1130 | 5960 | 0.90 | 6 | 1705 | 1290 | 1170 | 906 | ||||
800 | 1520/1330 | 6960 | 0.90 | 2065 | 1360 | 1170 | 936 | |||||
1000 | 1770/1550 | 8130 | 0.90 | 2390 | 1390 | 1220 | 1001 | |||||
1250 | 2090/1830 | 9690 | 0.90 | 2905 | 1450 | 1220 | 1081 | |||||
1600 | 2450/2140 | 11730 | 0.90 | 3405 | 1500 | 1270 | 1146 | |||||
2000 | 3050/2720 | 14450 | 0.70 | 4095 | 1560 | 1320 | 1326 | |||||
2500 | 3600/3200 | 17170 | 0.70 | 4835 | 1630 | 1370 | 1297 | |||||
SCB13 Series 10kV Dry-type transformers technical parameters | ||||||||||||
30 | 6 6.3 10 10.5 11 |
±5 or ±2x2.5 |
0.38 0.4 0.415 0.433 |
Dyn11 or Yyn0 |
150 | 710 | 2.3 | 4 | ||||
50 | 215 | 1000 | 2.2 | 468 | 1150 | 980 | 1030 | |||||
80 | 295 | 1380 | 1.7 | 684 | 1200 | 980 | 1060 | |||||
100 | 320 | 1570 | 1.7 | 756 | 1060 | 880 | 1090 | |||||
125 | 375 | 1850 | 1.5 | 978 | 1290 | 1000 | 1140 | |||||
160 | 430 | 2130 | 1.5 | 1032 | 1320 | 1000 | 1140 | |||||
200 | 495 | 2530 | 1.3 | 1200 | 1320 | 1000 | 1160 | |||||
250 | 575 | 2760 | 1.3 | 1380 | 1340 | 1100 | 1180 | |||||
315 | 705 | 3470 | 1.1 | 1572 | 1220 | 1300 | 1290 | |||||
400 | 785 | 3990 | 1.1 | 1788 | 1270 | 1300 | 1390 | |||||
500 | 930 | 4880 | 1.1 | 2316 | 1370 | 1350 | 1500 | |||||
630 | 1070 | 5880 | 0.9 | 2364 | 1640 | 1350 | 1500 | |||||
630 | 1040 | 5960 | 0.9 | 2736 | 1590 | 1450 | 1550 | |||||
800 | 1215 | 6960 | 0.9 | 2736 | 1590 | 1450 | 1550 | |||||
1000 | 1415 | 8130 | 0.9 | 3300 | 1670 | 1500 | 1630 | |||||
1250 | 1670 | 9690 | 0.9 | 6 | 4056 | 1750 | 1500 | 1770 | ||||
1600 | 1960 | 11730 | 0.9 | 4620 | 1860 | 1500 | 1770 | |||||
2000 | 2440 | 14450 | 0.7 | 5400 | 1860 | 1500 | 1990 | |||||
2500 | 2880 | 17170 | 0.7 | 6384 | 1980 | 1550 | 2040 |
Q: How do transformers been shipped?
A: Transformers always been delivered by ship,train or truck for oversea,which with main active body in bulk and accessories in wooden cases.
Q: Can your product be customerized?
A: Considering differences in voltage, frequency and other speciality of transformer product in different countries and regions,our product can be customerized according to your requirements.
Q: Do you offer guarantee for the products?
A: Yes. We offer at least two years guarantee for all of our transformers.
Q: Do you accept FAT(Factory Acceptance Test)?
A: Yes. It's available. We are responsible for each set transformer's testing.
Q: Do you assign engineer for after-sale service?
A: Yes. For our products,we all show after-sale guide installation adn question inquiry